| EPR
/ PVC
Three
Conductor Shielded
AEIC CS-6 MV-90 5kV
|
|
| A
P P L I C A T I O N S |
1.
2.
3.
4.
5. |
Raceways
Aerial (when properly supported)
Industrial plants
Primary power and distribution circuits
Utility substations
|
|
6.
7.
8.
9.
10.
|
Generating
plants
Wet or dry locations
Conduit, ducts, open tray or free air
Direct burial
Feeders, distribution, and branch circuits |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4.
5.
6. |
Conductors:
Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Ethylene propylene rubber (EPR)
Insulation Shield: Semi-conducting insulation screen
with a helically applied copper tape shield
Ground Wire: Stranded bare copper**
Cabling: Suitable lay with fillers |
|
7.
8.
9.
10. |
Jacket:
Sunlight resistant polyvinyl
chloride (PVC)
Temperature: 90°C continuous,
130°C emergency, 250°C short circuit
Voltage: 5000 Volts 100% & 133% insulation
level
Industry Approvals:
UL 1072 listed type MV-90
ICEA S-68-516
NEMA WC8
AEIC CS-6 |
|
Part
Number |
Size
AWG/
MCM |
No.
of
Strands |
Ground
Size
AWG |
Insul.
Thick.
in |
Jacket
Thick.
in |
Approx.
O.D.
inches |
Ampa-
city*
Rating |
Approx.
Weight
lbs/Mft |
| 100%
& 133% Insulation |
| 04-FD-3207 |
8 |
7 |
8 |
.090 |
.080 |
1.11 |
59 |
611 |
| 04-FD-3407 |
6 |
7 |
6 |
.090 |
.080 |
1.19 |
79 |
825 |
| 04-FD-3607 |
4 |
7 |
6 |
.090 |
.080 |
1.30 |
105 |
1052 |
| 04-FD-3807 |
2 |
7 |
6 |
.090 |
.080 |
1.43 |
140 |
1405 |
| 04-FD-3919 |
1 |
19 |
4 |
.090 |
.080 |
1.51 |
160 |
1625 |
| 04-FD-4019 |
1/0 |
19 |
4 |
.090 |
.080 |
1.60 |
185 |
1918 |
| 04-FD-4119 |
2/0 |
19 |
4 |
.090 |
.080 |
1.70 |
215 |
2180 |
| 04-FD-4219 |
3/0 |
19 |
3 |
.090 |
.110 |
1.87 |
250 |
2830 |
| 04-FD-4319 |
4/0 |
19 |
3 |
.090 |
.110 |
1.99 |
285 |
3365 |
| 04-FD-4437 |
250 |
37 |
3 |
.090 |
.110 |
2.09 |
320 |
3870 |
| 04-FD-4637 |
300 |
37 |
2 |
.090 |
.110 |
2.17 |
355 |
4640 |
| 04-FD-4837 |
350 |
37 |
2 |
.090 |
.110 |
2.32 |
395 |
5075 |
| 04-FD-5037 |
400 |
37 |
2 |
.090 |
.110 |
2.49 |
435 |
5795 |
| 04-FD-5337 |
500 |
37 |
1 |
.090 |
.110 |
2.61 |
485 |
6595 |
| 04-FD-5661 |
600 |
61 |
1 |
.090 |
.140 |
2.90 |
550 |
8090 |
| 04-FD-6061 |
750 |
61 |
1/0 |
.090 |
.140 |
3.12 |
615 |
9585 |
| 04-FD-6561 |
1000 |
61 |
1/0 |
.090 |
.140 |
3.56 |
705 |
11978 |
|
* Amps per conductor is in accordance
with NEC table 310-71, for three conductor copper cable isolated
in air, based on a conductor temperature of 90°C and ambient temperature
of 40°C. For other installation conditions, refer to the National
Electrical Code.
** Special ground wire configurations are available upon request
NOTE: May also be available with a Hypalon Jacket. |
|
|
JCH Wire & Cable... striving to exceed
customer expectations for quality, service, and value