XLP Unjacketed

Single Conductor
Non-Shielded MV-90 5kV
high voltage cable

high voltage XLP 5KV
A P P L I C A T I O N S
1.
2.
3.
4.
5.
Raceways
Aerial (when properly supported)
Industrial plants
Primary power & distribution circuits
Utility substations
6.
7.
8.
9.
10.
Generating plants
Dry locations
Conduit, ducts, open tray, or open air
Airport lighting (sizes 8-4)
Areas where space is limited
S P E C I F I C A T I O N S
1.
2.

3.
4.
Conductor: Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Cross-linked polyethylene (XLP)
Temperature: 90°C continuous, 130°C emergency, 250°C short circuit
5.
6.
Voltage: 5000 Volts 100% insulation level
Industry Approvals:
UL 1072 listed type MV-90 Dry,
ICEA S-66-524, NEMA WC 7,
Conforms to FAA L-824-C,
Airport Lighting Cable Specifications
Part Number Size
AWG/
MCM
No. of
Strands
Insul.
Thick.
in
Approx.
O.D.
inches
Ampacity*
Rating
Approx.
Weight
lbs/Mft
04-AA-1332 8** 7 .110 0.39 55 90
04-AA-1334 6** 7 .110 0.42 75 125
04-AA-1336 4** 7 .110 0.47 97 180
04-AA-1338 2 7 .110 0.53 130 260
04-AA-1339 1 19 .110 0.57 155 325
04-AA-1340 1/0 19 .110 0.62 180 400
04-AA-1341 2/0 19 .110 0.66 205 490
04-AA-1342 3/0 19 .110 0.71 240 605
04-AA-1343 4/0 19 .110 0.77 280 750
04-AA-1344 250 37 .120 0.83 315 890
04-AA-1348 350 37 .120 0.94 385 1215
04-AA-1353 500 37 .120 1.05 475 1695
04-AA-1360 750 61 .130 1.27 600 2500
04-AA-1365 1000 61 .130 1.43 690 3320
* Amps per conductor is in accordance with NEC table 310-73, for three conductors in an isolated conduit in air, based on a conductor temperature of 90°C and ambient temperature of 40°C.
** AWG size 8,6 and 4 conform to airport lighting specification FAA L-824-C
NOTE: May also be available with a Hypalon Jacket.

 