Building Wire | FR-EPR Use-2

Contact Us


Las Vegas, NV


Phone: (800) 827-1144

Phone: (702) 639-4000

Fax: (702) 639-4001




Reno, NV


Phone: (800) 827-6116

Phone: (775) 850-3000

Fax: (775) 850-3001

FR-EPR Insulated

RHH - RHW-2 or USE-2
Single Conductor, 600V


FR-EPR insulated building wire

FR-EPR insulated building wire
A P P L I C A T I O N S
1.
2.
Aerial installations
Cable tray
3.
4.
Raceways
Direct burial
S P E C I F I C A T I O N S
1.
2

3.

4.
Conductor: Stranded soft-drawn bare copper
Insulation
:Flame retardant
ethylene propylene (EPR)
Temperature: 90°C dry or wet, 130°C emergency, 250°C short circuit
Voltage: 600 Volts
5.




6.
Industry Approvals: UL list, UL VW-1
ICEA S-68-516
OSHA accepted
IEEE 383 Flame Test
ICEA-T-29-520 210,000 BTU test
Jacket Color: Black
Part
Number
Size
AWG
No. of
Strands
Insul.
Thick
in.
FREP
Insul.
Diam.
in.
Bare Soft
Copper
Cond.
Diam. in.
Approx.
Weight
lbs/Mft
Copper
Weight
lbs/Mft
02-CB-1326 14** 7 .045 .17 .07 25 13
02-CB-1328 12 7 .045 .19 .09 34 20
02-CB-1330 10 7 .045 .21 .12 48 32
02-CB-1332 8 7 .060 .27 .15 78 51
02-CB-1334 6 7 .060 .31 .18 114 81
02-CB-1336 4 7 .060 .36 .23 169 129
02-CB-1338 2 7 .060 .42 .29 254 205
02-CB-1339 1 19 .080 .49 .33 327 258
02-CB-1340 1/0* 19 .080 .53 .37 402 326
02-CB-1341 2/0* 19 .080 .58 .41 495 411
02-CB-1342 3/0* 19 .080 .63 .46 613 518
02-CB-1343 4/0* 19 .080 .69 .52 759 653
02-CB-1344 250* 37 .095 .77 .56 905 772
02-CB-1348 350* 37 .095 .87 .67 1235 1081
02-CB-1353 500* 37 .095 1.00 .80 1728 1544
02-CB-1360 750* 61 .110 1.22 .98 2573 2316
02-CB-1365 1000* 61 .110 1.37 1.13 3381 3088
* Single conductor 1/0 AWG and larger are listed "for CT Use" in accordance with NEC Article 318
** Not rated type USE

 

JCH Wire & Cable... striving to exceed
customer expectations for quality, service, and value