| EPR
/ CSPE - USE-2
RHH
- RHW
|
|
| A
P P L I C A T I O N S |
1.
2. |
For lighting
and power circuits
Switchboards |
|
3.
4.
5. |
Raceways
and ducts
Direct burial
Cable trays |
|
| S
P E C I F I C A T I O N S |
1.
2
3.
4.
5. |
Conductor:
Stranded soft-drawn coated copper
Insulation: Ethylene propylene rubber(EPR)
Jacket: Chlorosulfonated polyethylene (CSPE)
Temperature: 90°C dry or wet
Voltage: 600 Volts
|
|
6.
7. |
Jacket
Color: Black
Industry Approvals:
UL standard 44 & 854
UL VW-1 Vertical flame test
ICEA S-68-516
Federal J-C-30B
IEEE 383 |
|
|
|
* Single conductor 1/0 AWG and larger are listed "for
CT Use" in accordance with NEC Article 318
** Amperes Per Conductor is in accordance with NEC table 310-16 for not more than three
conductors in a raceway as RHH-RHW and not more than three conductors in a raceway or
cable in earth is USE and ambient temperature of 30°C. Over current protection shall not
exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper.
§Not rated USE. |
|