Aluminum Interlocked

 

Armor Power Cable
Three Conductor Type MC, 600V, XHHW/PVC
three condcutor type mc

 
A P P L I C A T I O N S
1.
2.
3.
4.
Power and lighting circuits
Feeders
Direct burial
Raceways
5.
6.
7.
8.
9.
Control and signal circuits
Aerially (when supported by a messenger)
Class I and II, Division 2 hazardous locations
Class III Division 1 and 2 hazardous locations
Suitable for use in trays or racks
S P E C I F I C A T I O N S
1.
2.
3.


4.
5.
Conductor: Stranded soft-drawn bare copper
Insulation: Cross-linked polyethylene (XLP)
Cabling: Insulated conductors are cabled with a ground wire, (fillers where needed) and a binding tape
Ground Wire: Stranded bare copper
Armor: Aluminum interlocked**
6.

7.
8.
9.
Jacket: Sunlight and flame resistant polyvinyl chloride (PVC)
Temperature:
90°C dry, 75°C wet
Voltage:
600 Volts
Industry Approvals:
UL type MC approved for CT use
IEEE 383 flame test
Part
No.
Size
AWG/
MCM
No. of
Conds.
Insul.
Thick
inches
Ground
Wire
Size
AWG
Jacket
Thick
inches
Approx.
O.D.
inches
Amps.*
Dry/Wet
90°C/75°C
Approx.
Weight
lbs/Mft
05-AA-3203 8 3 .045 10 .050 0.81 55/50 410
05-AA-3403 6 3 .045 8 .050 0.88 75/65 550
05AA-3603 4 3 .045 8 .050 0.98 95/85 740
05-AA-3803 2 3 .045 6 .050 1.17 130/115 1100
05-AA-3903 1 3 .055 6 .050 1.30 150/130 1350
05-AA-4003 1/0 3 .055 6 .050 1.38 170/150 1600
05-AA-4103 2/0 3 .055 6 .050 1.48 195/175 1900
05-AA-4203 3/0 3 .055 4 .050 1.59 225/200 2400
05-AA-4303 4/0 3 .055 4 .050 1.73 260/230 2900
05-AA-4403 250 3 .065 4 .060 1.87 290/255 3400
05-AA-4803 350 3 .065 3 .060 2.10 350/310 4400
05-AA-5303 500 3 .065 2 .060 2.38 430/380 6100
05-AA-6003 750 3 .080 1 .075 2.87 535/475 8800
05-AA-6503 1000 3 .080 1/0 .085 3.25 615/545 11500